ICA UPS SE Series Because the UPS is the true on-line system, conditioned power is provided continuously to the attached load. The UPS constantly regulates and filter the AC input voltage and supply a clean and stable AC voltage to the output and charge the batteries. When the AC input voltage low or loss, the UPS protects the load instantaneously and supply a stable AC voltage without any transfer time. Here are some of the models and capacity of UPS SE Series.

Specification
Model UPS SE1000 UPS SE2000 UPS SE3000
Capacity 1000 VA / 700 W 2000 VA / 1200 W 3000 VA / 2100 W
AC Voltage 110 ~ 285 V / 160 ~ 285 V 110 ~ 285 V / 160 ~ 285 V 110 ~ 285 V / 160 ~ 285 V
AC Frequency 50 ± 5 Hz 50 ± 5 Hz 50 ± 5 Hz
AC Protection 6 A 12A 16 A
DC Voltage 36 V 96 V 96 V
DC INT Battery 3 x 12 V, 7 Ah 8 x 12 V, 7 Ah 8 x 12 V, 7 Ah
DC Protection FUSE FUSE FUSE
CHG Topology SWITCHING REGULATION SWITCHING REGULATION SWITCHING REGULATION
CHG Floating Voltage 40.8 V 108.8 V 108.8 V
INV Waveform SINEWAVE SINEWAVE SINEWAVE
INV Distorsion < 3% THD < 3% THD < 3% THD
INV Topology PULSE WIDTH MODULATION (PWM) PULSE WIDTH MODULATION (PWM) PULSE WIDTH MODULATION (PWM)
INV Voltage 220 ± 1% V 220 ± 1% V 220 ± 1% V
INV Frequency 50 ± 1% Hz 50 ± 1% Hz 50 ± 1% Hz
INV Efficiency > 83% > 85% > 85%
Transfer Time When AC In Loss 0 ms 0 ms 0 ms
Transfer Time STS 2 ms Inverter to Bypass, 0 ms Back To Inverter 2 ms Inverter to Bypass, 0 ms Back To Inverter 2 ms Inverter to Bypass, 0 ms Back To Inverter
Back Up Time 10 min 10 min 10 min
BZR AC Input Abnormall INTERMITTENT SOUND WITH 4 SECONDS INTERVAL INTERMITTENT SOUND WITH 4 SECONDS INTERVAL INTERMITTENT SOUND WITH 4 SECONDS INTERVAL
BZR Battery Low INTERMITTENT SOUND WITH 1 SECONDS INTERVAL INTERMITTENT SOUND WITH 1 SECONDS INTERVAL INTERMITTENT SOUND WITH 1 SECONDS INTERVAL
Opera Temp 0 - 40 °C 0 - 40 °C​ 0 - 40 °C
Dimension(DxWxH) 412 x 144 x 213 mm 470 x 191 x 338 mm 470 x 191 x 338 mm
Weight 16 Kg 35 Kg 36 Kg